Functions overview
- Environmentally-friendly, economic cooling solution
- High efficiency
- Precise temperature control
- Simple operation with menu navigation
- Robust stainless construction
- Reliable continuously operation with warning functions
- Easy to fill and empty
- Illuminated filling level indicator
- Bright, large OLED display
- USB and RS232 interfaces
| Cooling capacity |
|
||||||||
| Refrigeration machine | air-cooled, natural refrigerant | ||||||||
| Refrigerant 1st stage | R-290 (A3, H220) | ||||||||
| Refrigerant quantity 1st stage | 0,07 kg |
| Delivery capacity pressure pump max. | 14 l/min; 0,25 bar |
| Delivery capacity suction pump max. | 10,5 l/min; 0,17 bar |
| Pump connection | M16x1 AG male |
| Pump speed adjustable | no |
| Pump type | Yes |
| Pump characteristics | Pressure and suction pump, speed not variable |
| Permissible ambient temperature | 5...40 °C |
| Sound pressure level | 59 dB(A) |
| Filling volume min. | 1,5 l |
| Expansion volume | 1 l |
| Power supply | 208-240V 1~/2~ 50/60Hz |
| Current consumption max. | 3,5 A |
Please take further technical information as well as information about the scope of delivery, accessories and peripheral devices from the PDF data sheet. In cases of doubt the details given in there apply. If nothing to the contrary is quoted then the performance data referred is at an ambient temperature of 20°C.
Please observe the notes on installation and/or the space requirements of our products.
The following voltage and frequency tolerances apply based on EN60034-1:
Voltage +/- 5% for a frequency tolerance at the same time of +/- 2%
Examples to illustrate this: Not permissible, for example. is -5% on the voltage and +2% on the frequency. Permissible, on the other hand, are tolerances of -5% on the voltage and -2% on the frequency.
We reserve the right to make technical changes and correct errors. Illustrations can deviate from the original.